Product Overview & Working Principle

 

A Current Transformer (CT) is a specialized electrical instrument transformer designed to convert high primary alternating current (AC) into a proportional, standardized secondary current, typically 1A or 5A, for electrical measurement and protection systems. It provides galvanic isolation between high-voltage power lines and low-voltage monitoring instrumentation, ensuring safe operation for power meters, data loggers, and protective relays.
Depending on the design and application, current measurement solutions include conventional solid-core CTs, split-core CTs, and Rogowski coils. Each configuration has distinct installation requirements, output characteristics, and application considerations.
Working Principle
A conventional current transformer operates through electromagnetic induction (Faraday's Law of Induction). In a typical window-type CT, the primary conductor passing through the magnetic core acts as a single-turn primary winding. The alternating primary current generates magnetic flux in the core, inducing a proportional current in the secondary winding according to the transformer turns ratio.
The secondary current is determined by the primary current and the designed turns ratio. Specified accuracy depends on core characteristics, winding design, rated burden, and operating conditions.
Core Construction
Depending on the required accuracy class and application, magnetic cores utilize grain-oriented silicon steel (CRGO), nanocrystalline materials, or other specified magnetic alloys. Core material selection is evaluated alongside core geometry, winding design, and rated operating conditions to meet required measurement characteristics.
Insulation & Mechanical Construction
CT insulation and enclosure designs vary according to product structure and rated electrical requirements. Available construction options include epoxy-resin cast insulation, molded engineering thermoplastic housings, and application-specific split-core assemblies.
The insulation system, enclosure material, and mechanical design are selected according to the intended installation environment and applicable electrical standards.

 
 
Technical Specifications & Product Series

 

Solid-Core (Ring) Current Transformer
Solid-core current transformers feature a closed magnetic core and are commonly integrated into electrical distribution panels, switchgear assemblies, and fixed metering installations.

Parameter

Specification

Primary Current Range

5A to 5000A AC (model dependent)

Secondary Output

1A or 5A; low-voltage outputs available upon request

Accuracy Class

IEC 61869-2 Class 0.2S, 0.5, 1.0 (model dependent)

Rated System Voltage

Up to 0.72kV (IEC) / 600V (UL)

Configuration

Solid-core / Ring type

Typical Applications

Energy metering, switchgear assemblies, distribution panels, substation metering

CAD Files

Download STEP / IGES

 

Split-Core Current Transformer
Split-core current transformers feature an opening magnetic core that allows installation around existing conductors without disconnecting the circuit. They are commonly used in retrofit metering and energy monitoring installations.

Parameter

Specification

Primary Current Range

100A to 5000A AC (model dependent)

Secondary Output

1A or 5A; low-voltage outputs available upon request

Accuracy Class

Class 0.5, 1.0, 3.0 (model dependent)

Rated System Voltage

Up to 0.72kV (IEC) / 600V (UL)

Configuration

Hinged or separable core design

Typical Applications

Retrofit sub-metering, energy monitoring, electrical distribution systems

CAD Files

Download STEP / IGES

 

Rogowski Coil

Parameter

Specification

Primary Current Range

500A to 50000A AC (model dependent)

Output Configuration

Coil output or integrated signal-processing output

Output Sensitivity

85mV to 150mV per 1000A (frequency and signal-processing dependent)

Accuracy Class

Class 0.5, 1.0 (IEC 61869-2 compliant)

Rated Application Voltage

Up to 1000V (Isolated)

Typical Applications

High-current monitoring, power quality measurement, industrial energy monitoring

CAD Files

Download STEP / IGES

 

 

Construction, Materials & Manufacturing Control

Current transformer manufacturing involves magnetic core preparation, secondary winding, insulation assembly, enclosure processing, and electrical testing.

Magnetic Core Processing: Core materials are selected according to transformation ratio, accuracy class, and operating conditions. For applicable models, core cutting and joint preparation are executed per strict manufacturing procedures.

Secondary Winding: Utilizes specified enameled copper wire. Winding turns and wire specifications are monitored via CNC equipment to maintain required ratio accuracy and eliminate leakage reactance.

Insulation & Enclosure Assembly: Incorporates vacuum-cast epoxy-resin systems or molded engineering thermoplastics (Polycarbonate/PBT) to eliminate internal voids and ensure high dielectric strength (≥ 3kV at 50Hz for 1 minute).

 

Quality Control & Electrical Verification:

Incoming Inspection: Core materials, copper wire, and insulation polymers.

Production Control: Winding turns, assembly dimensions, and component identification.

Electrical Testing: 100% routine testing for transformation ratio, ratio error, phase displacement, and insulation withstand voltage per IEC 61869-2 / IEEE C57.13.

Final Inspection: Dimensions, terminal markings (P1/P2, S1/S2), and polarity verification.

LZZBJ9-10Q B6 Indoor Single-phase Current Transformer

 

Technical Selection & System Compatibility

 

 

Transformation Ratio: The CT ratio must match the expected primary current and meter/relay input requirements (e.g., 600A/5A ratio of 120:1).


Accuracy Class & Burden:
Measuring CTs (0.2S, 0.5, 1.0): Focus on linearity near normal operating loads (1% to 120% of In). Total burden (Zb = Rw + Rm) must remain within rated VA limits.
Protection CTs (5P, 10P): Engineered to maintain linearity at high multiples of rated current, taking Accuracy Limit Factor (ALF) into account.
Aperture & Installation Clearance: Verify inner window dimensions against cable outer diameter or busbar width/thickness. Provide mechanical clearance details for retrofits.
Polarity & Terminals: Verify terminal markings (P1/P2 and S1/S2) to ensure correct directional power measurement and protective relay coordination.
Thermal Limits: Verify continuous operating temperature range (typically -25°C to +70°C) and short-time thermal current rating (Ith) for each specific model.

 

 

Frequently Asked Questions

 

 

Q: What happens if the secondary circuit of an energized CT is left open?

A: Opening the secondary circuit while primary current is flowing forces the magnetic core into deep saturation, generating dangerously high voltage spikes across open terminals. This risks severe insulation breakdown, equipment damage, and electric shock. Always short-circuit secondary terminals before disconnecting meters or relays.

Q: Can split-core CTs achieve Class 0.2S accuracy?

A: Standard split-core CTs typically achieve Class 0.5 or 1.0 due to air-gap reluctance at mating core surfaces. For strict revenue-grade Class 0.2S compliance, solid-core (ring) CTs are recommended, though specialized precision split-core models can be reviewed upon request.

Q: What is the difference between measuring CTs and protection CTs?

A: Measuring CTs maintain high accuracy under normal operating currents (1% to 120%) and saturate during faults to protect downstream meters. Protection CTs maintain linearity up to high multiples of rated current to supply accurate fault data to protective relays.

Q: What standards apply to current transformers?

A: Design and testing comply with applicable sections of the IEC 61869 series or IEEE C57.13 standards, utilizing UL-recognized flame-retardant materials. Specific compliance and test documentation can be verified per product series.

Q: How do I select the correct CT ratio and rated burden?

A: Determine maximum primary current, secondary output (1A or 5A), and calculate total secondary burden (meter load plus lead wire resistance). Select a CT with a rated VA and accuracy class that encompasses these parameters.

Q: What information is required for a customized current transformer?

A: Provide primary current, secondary output, accuracy class, rated burden, system voltage, installation dimensions, and application details (metering vs. protection).

modular-1
Request a Technical Proposal & Quote

To receive a commercial quotation, technical datasheets, and instant 2D/3D CAD drawings within 24 hours, please submit your engineering specifications:

Transformation Ratio: (e.g., 600A / 5A or 400A / 1A)

Secondary Output: (1A, 5A, or 333mV)

Accuracy Class: (e.g., Class 0.2S, Class 0.5, or Class 5P10)

Rated Burden: (Required VA rating)

Configuration: (Solid-Core, Split-Core, or Rogowski Coil)

Installation Dimensions: (Cable diameter or busbar dimensions)

With abundant experience, Wenzhou Best Imp. & Exp. is one of the most professional current transformer manufacturers and suppliers in China. Please feel free to buy durable current transformer made in China here from our factory. Quality products and good service are available.