Product Overview
An Outdoor Voltage Transformer (VT), also designated as an Outdoor Potential Transformer (PT), is a high-voltage electromagnetic instrument transformer engineered to step down primary transmission and distribution line potentials into safe, standardized secondary signals (100V, 110V, or 120V) for revenue metering, voltage monitoring, instrumentation, and protective relaying schemes.
Built for uncompromised outdoor switchyard performance, outdoor VTs provide vital electrical isolation between high-voltage lines and low-voltage control infrastructure.
-
JDZ(F)-35W2 Outdoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 40.5/95/200kV
Rated frequency: 50Hz or 60Hz -
JDZXW-35 Outdoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-20 13 and IEC60044-2 standards
Rated insulation level: 40.5/95/185kV
Rated frequency: 50Hz or 60Hz
Operating on the fundamental principle of electromagnetic induction, the primary winding connects in parallel across the high-voltage conductor, while the secondary winding delivers a proportional, phase-aligned output signal to connected control devices.
Primary Winding: Wound with oxygen-free copper and engineered to withstand continuous thermal currents and transient overvoltage spikes.
Secondary Windings: Modular winding configurations supporting simultaneous revenue metering, system protection, and residual voltage (broken-delta) monitoring.
Magnetic Core
Assembled from high-permeability cold-rolled grain-oriented silicon steel (CRGO) using step-lap mitred joints to minimize core loss and maintain high linearity during fault conditions.
Insulation Structure
Hydrophobic Cycloaliphatic Epoxy Resin (HPWR) vacuum-cast via Automated Pressure Gelation (APG) to eliminate internal micro-voids and prevent tracking under intense solar UV exposure.
External Enclosure
Structural steel mounting bases finished with hot-dip galvanizing (min. 85 um) and marine-grade aluminum secondary junction boxes (IP55/IP66).
Technical Specifications
|
Technical Parameter |
Standard Specification |
|
Product Type |
Outdoor Voltage Transformer (VT / PT) |
|
Equipment Highest Voltage (Um) |
12 kV / 24 kV / 36 kV (Custom higher ratings available) |
|
Rated Primary Voltage |
10 kV to 33 kV |
|
Rated Secondary Voltage |
100V, 110V, 120V (Dual-ratio configurations supported) |
|
Secondary Winding Arrangement |
Multi-tap configurable (Metering, Protection, Residual Voltage) |
|
Metering Accuracy Class |
0.2S, 0.5 |
|
Protection Accuracy Class |
3P, 6P |
|
Rated Burden |
15 VA to 150 VA per winding |
|
Rated Voltage Factor |
1.2 Continuous, 1.9 for 30s (or 8h per network grounding design) |
|
Power-Frequency Withstand Voltage |
28 kV to 70 kV (1 min) |
|
Lightning Impulse Withstand Voltage |
75 kV to 170 kV (1.2/50 us wave) |
|
Minimum Creepage Distance |
>= 25 mm/kV up to 31 mm/kV (IEC 60815 Class III / IV) |
|
Ambient Operating Temperature |
-40 deg C to +55 deg C |
|
Design & Test Standards |
IEC 61869-1, IEC 61869-3, IEEE Std C57.13 |
Secondary Winding Configurations
Metering Winding
Dedicated to revenue meters and billing instruments. High-precision 0.2S classes guarantee measurement accuracy even under low partial loads (25% to 100% rated burden).
Protection Winding
Optimized for protective relay systems, designed to maintain response fidelity and accuracy under heavy fault transient conditions.
Residual Voltage Winding (Broken-Delta)
Auxiliary secondary winding configured for earth-fault detection and ferroresonance damping in ungrounded or Petersen-coil-grounded networks.
Outdoor Substations & Switchyards: Feeds precise voltage data to control rooms for primary grid automation and monitoring.
Renewable Energy Step-Up Substations: Widely integrated into solar PV and wind farm collector substations.
Severe Environmental Conditions: Engineered for high altitudes, coastal salt-fog zones, and heavy industrial pollution by extending creepage distances up to Pollution Class IV per IEC 60815 guidelines.

Technical Selection Guide
Insulation Coordination
Match equipment highest voltage (Um) and basic impulse insulation level (BIL) to local grid parameters and altitude derating factors per IEC 60071.
Burden & Metering Class Integration
Ensure total connected secondary burden (relays, meters, and wiring cables) remains strictly within the rated VA operating limits of the chosen accuracy class.
Ferroresonance Mitigation
For ungrounded networks prone to ferroresonant oscillations, specify auxiliary broken-delta windings with verified thermal ratings and damping provisions.
Mechanical Retrofitting & Footprint Matching
For substation upgrade or replacement projects, verify mounting flange bolt-hole pitch dimensions, terminal clearances, and enclosure protection ratings against existing structural steel frameworks.

APG Vacuum Casting: Automated Pressure Gelation chambers maintain strict thermal and vacuum (< 1 Torr) control to eliminate internal micro-voids and prevent partial discharge degradation under intense solar UV exposure.
Partial Discharge (PD) Screening: Routine testing conducted on 100% of production units inside electromagnetic shielding enclosures; apparent charge extinction threshold is strictly verified below 10 pC at 1.2 * Um / sqrt(3).
Dielectric & Error Verification: Power-frequency withstand tests, polarity checks, and automated bridge comparator error measurements (25%, 50%, 100% burden) executed with traceability to national calibration standards.
Hot-Dip Galvanizing: External mounting bases and support brackets treated with hot-dip galvanizing (min. 85 um coating thickness) complying with ISO 1461.
Export Maritime Packaging: Packed in fumigation-free, ISPM 15 compliant plywood crates with internal timber cradles, sealed within heavy-duty moisture barrier bags, and packed with active silica gel desiccants.
Customization & Engineering Support
We provide full technical customization for non-standard substation upgrades and replacement projects. Available tailoring parameters include:
Custom primary/secondary voltage ratios and multi-tap configurations
Non-standard mounting bracket dimensions and seismic-braced enclosures (IEEE 693 compliance)
Tailored creepage distances for extreme coastal or heavy industrial environments
Comprehensive submittal documentation packages including 2D/3D CAD drawings (STEP, PDF) and certified routine test reports
Frequently Asked Questions

Request a Technical Quotation
To receive a formal commercial and technical proposal within 24 hours, please submit your project specifications:
Electrical System: System Highest Voltage (Um), Primary & Secondary Voltage Ratios, System Grounding Type
Performance Requirements: Accuracy Class (0.2S, 0.5), Rated Burden (VA), Voltage Factor
Environmental Data: Site Altitude, Ambient Temperature Range, Pollution Level / Creepage Distance
Mechanical Constraints: Flange Bolt-Hole Pitch Dimensions, Quantity Required
Project Details: Destination Port, Target Delivery Date, and Applicable Standards (IEC / IEEE)