Product Overview & Application Scope
A voltage transformer (VT)--widely recognized as a potential transformer (PT) in North American engineering terminology--is a specialized instrument transformer engineered to step down high-voltage power system levels to safe, standardized secondary signals. It provides essential inputs for electrical measurement, billing-grade energy metering, and protective relaying while ensuring complete galvanic isolation between hazardous high-voltage primary circuits and low-voltage secondary instrumentation.
-
JDZX9-35 Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 40.5/95/185kV
Pollution class: class Ⅱ
Rated frequency:... -
JSZY16-35R Voltage TransformerThe JSZY16-35R voltage transformer manufactured by Wenzhou Best Imp. & Exp. Co., Ltd is specifically designed for outdoor switchgear. Featuring fuse protection for the primary winding, this...
-
JDZ(F)-35W2 Outdoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 40.5/95/200kV
Rated frequency: 50Hz or 60Hz -
JDZXW-35 Outdoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-20 13 and IEC60044-2 standards
Rated insulation level: 40.5/95/185kV
Rated frequency: 50Hz or 60Hz -
JDZX11-35 Indoor Voltage TransformerJDZX11-35R voltage transformer is a 35kV voltage transformer, belonging to single-phase cast-in-place indoor voltage transformer and dry-type with fuse voltage transformer. It is suitable for...
-
JSZVR-10W Indoor Three-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZX18-10R1 Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZ8-10R Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZ(J)-10Q Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZC-10 Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZX10-10 Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz -
JDZX9-10Q Indoor Single-phase Voltage TransformerThe voltage transformers are in accordance with GB20840.3-2013 and IEC60044-2 standards
Rated insulation level: 12/42/75, 7.2/32/60kV
Rated frequency: 50Hz or 60Hz
Working Principle & Construction Architecture
Electromagnetic Working Principle
Operating strictly on Faraday's law of electromagnetic induction, a voltage transformer transforms system alternating voltage via core flux coupling:
Primary Excitation: The primary winding connected to the high-voltage busbar establishes an alternating magnetic flux within the core.
Secondary Induction: The core flux induces a proportional electromotive force in the secondary winding, governed precisely by the turns ratio.
Performance Determinants: Actual secondary output accuracy and phase displacement are governed by the magnetic properties of the core material, internal winding impedance, and the total connected burden.
Construction Materials & Components
Magnetic Core: Built from cold-rolled grain-oriented (CRGO) silicon steel laminations with precision mitered joints to minimize core losses and maximize magnetic permeability.
Winding Conductors: Wound using electrolytic-grade copper conductors designed to withstand thermal loads and electrodynamic short-circuit forces.
Insulation System:
Indoor Units: High-grade vacuum-pressure impregnated (VPI) epoxy resin systems or class-rated insulating structures.
Outdoor Units: Cycloaliphatic epoxy resin castings providing exceptional tracking resistance, UV stability, and outdoor weathering durability.
Technical Specifications
|
Parameter Category |
Standard Indoor Unit (MV) |
Cast Resin Outdoor Unit |
Engineering Notes & Compliance |
|
Primary Voltage Range |
0.6 kV to 35 kV |
Up to 40.5 kV |
Matches system operating voltage |
|
Secondary Voltage |
100V, 110V, 120V (Adjustable) |
100V / sqrt(3), 110V / sqrt(3) |
Standard instrumentation interface |
|
Rated Frequency |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
Grid frequency synchronization |
|
Metering Accuracy Class |
0.2, 0.5, 1.0 |
0.2S, 0.5S |
High linearity for billing meters |
|
Protection Accuracy Class |
3P, 6P |
3P, 6P |
Maintains saturation accuracy under faults |
|
Rated Burden |
10 VA to 100 VA |
25 VA to 150 VA |
Total connected instrument/relay load |
|
Insulation Level (BIL) |
Up to 75 kV BIL |
Up to 200 kV BIL |
Dielectric withstand capability |
Types & Configurations
Indoor Voltage Transformers
Compact footprint designed for integration inside enclosed medium-voltage switchgear cubicles and distribution panels, emphasizing clearance management and thermal dissipation.
Outdoor Voltage Transformers
Robust external insulation structures optimized for substation environments, featuring extended creepage distances to withstand high pollution levels, heavy humidity, and wind-driven rain.
Metering vs. Protection Units
Configured with specific core saturation curves; metering classes maintain high precision near normal operating voltages, while protection classes sustain accurate ratio output during heavy system fault currents.
Multi-Winding Configurations
Available with independent secondary windings allocated separately for billing metering, local monitoring instruments, and protective relay schemes.
To ensure long-term operational reliability and accurate signal reproduction, engineering selection must evaluate:
Ratio & Burden Matching: Total active burden (meters, relays, and secondary connection wiring) must not exceed the rated burden limit to prevent exceeding accuracy class error limits.
Voltage Factor & Thermal Limit: Select the voltage factor (e.g., 1.2 continuous, 1.5 for 30 seconds) based on system grounding configurations (e.g., solidly grounded vs. ungrounded systems) to prevent thermal degradation during overvoltage swells.
Mechanical Integration: Verify mounting hole dimensions, phase-to-phase air clearances, busbar terminal orientation, and physical compartment envelopes--especially critical when retrofitting legacy switchgear panels.


Winding & Core Assembly: Automated CNC tension-controlled winding combined with precision core stacking to eliminate micro-gaps and control magnetic characteristics.
Resin Processing: Automated Pressure Gelation (APG) and high-vacuum casting processes eliminate internal voids, securing partial discharge (PD) suppression.
Factory Acceptance Testing (FAT): Every production batch undergoes rigorous routine testing, including:
Winding DC resistance and turns-ratio verification.
Polarity and phase displacement checks.
Power-frequency dielectric withstand voltage testing.
Partial discharge measurement (maintaining background noise floor strictly below specification limits).
Type Testing: Certified design verification reports available covering temperature-rise tests, lightning impulse withstand, and short-circuit dynamic stability tests.
Customization & Engineering Support
Retrofit Solutions
Engineering evaluation of customer-supplied CAD drawings, dimensional sketches, or nameplate data to design custom mounting adapter brackets and terminal arrangements for existing switchgear replacements.
Electrical Modifications
Custom multi-tap secondary windings, dual-ratio specifications, and harmonic-mitigating core designs tailored for heavy industrial or renewable energy (solar/wind inverter) applications.
Deliverables
Provision of 2D/3D CAD models (STEP/IGES), complete electrical schematic diagrams, and individual certified test certificates shipped with every hardware batch.
Frequently Asked Questions

Request a Quote
To receive a formal engineering evaluation and commercial quotation, please provide the following parameters:
System Parameters: Primary Voltage, Secondary Voltage, Rated Frequency, and System Grounding Type.
Performance Requirements: Accuracy Class (e.g. 0.2 for metering, 3P for protection) and Rated Burden (VA).
Winding Configuration: Number of secondary windings, ratio per winding, and specific application allocations.
Installation Environment: Indoor or Outdoor, ambient temperature range, altitude, and pollution conditions.
Mechanical Constraints: Mounting footprint dimensions, terminal orientation, or specific switchgear model for retrofits.
Order Details: Required batch quantity, destination market, applicable standards, and target delivery schedule.
With abundant experience, Wenzhou Best Imp. & Exp. is one of the most professional voltage transformer manufacturers and suppliers in China. Please feel free to buy durable voltage transformer made in China here from our factory. Quality products and good service are available.