Product Overview & Application Scope

 

A Medium Voltage Loadbreak Switch (LBS) is a mechanical switching device engineered to make, carry, and interrupt specified normal load currents in medium-voltage power distribution systems. It controls distribution circuits and safely isolates electrical equipment during scheduled operational switching.
Depending on its configuration and rated characteristics, the loadbreak switch provides specified short-circuit making and short-time withstand capabilities. For heavy short-circuit fault interruption, it operates in coordination with downstream protective devices such as current-limiting fuses or upstream circuit breakers.
Standard voltage configurations cover 12kV, 24kV, and 38kV product classes for modern distribution networks.

 
  • 24kV 630A 3P 2 Position IEEE Loadbreak Switch
    The 24kV 630A Three Phase Oil Immersed Loadbreak Switch is engineered for medium-voltage power distribution systems requiring dependable three-phase load control inside oil-filled transformers....
  • Four-Position Oil-Immersed Loadbreak Switch
    The Four-Position Oil-Immersed Loadbreak Switch is designed for medium-voltage oil-filled distribution transformers, providing flexible circuit selection and switching functions for primary-side...
  • 25kV 630A Single Phase Flip Type Transformer Loadbreak
    The 24kV 630A Oil Immersed Loadbreak Switch is a critical switching device used in medium-voltage distribution transformer systems. It is designed to safely make and break load current under...
  • 25kV 630A Two Position Loadbreak Switch
    The 24kV 630A Single Phase Oil Immersed Loadbreak Switch is a specialized switching device developed for medium-voltage oil-filled transformer applications. It enables safe switching and...
  • 630A 24KV Flip Type ANSI Load Break Switch
    The 24kV 630A Single Phase Oil Immersed Loadbreak Switch is a specialized switching device developed for medium-voltage oil-filled transformer applications. It enables safe switching and...
  • 35kV Oil Immersed Loadbreak Switch
    The 35kV Oil Immersed Loadbreak Switch is a medium-voltage switching component developed for safe and efficient current switching inside oil-filled electrical equipment. It is widely utilized in...
  • 630A 40.5kV Pad Mounted Transformer Loadbreak Switch
    The two-position series oil-immersed load switch is suitable for combined transformers with an AC frequency of 50/60 Hz and a maximum voltage of 40.5 kV or below. It serves as a control device for...
  • 630A 35KV 2 Pos Oil Loadbreak Switch
    The 630A 35kV 2 Position Flip Top Type Oil Loadbreak Switch is a medium-voltage switching solution developed for oil-insulated transformer systems and compact power distribution equipment....
  • 630A 35KV 4 Position Oil Loadbreak Switch
    The 630A 35kV 4 Position Oil Loadbreak Switch is a high-performance medium-voltage switching device engineered for oil-filled transformer applications and compact electrical distribution systems....
  • 35kV Four Position Loadbreak Switch
    The 35kV Four Position Loadbreak Switch switch is used in combination transformers. The load switch is available in four-position, with the four-position switch further classified into T-type,...
  • 25kV Oil Lbor Switch
    The two-position oil-immersed load switch is mainly used in pad mounted transformers. It has a spring operating mechanism and is a three-phase switch, capable of performing load opening and...
  • 35kV Lbor 4 Position Pad Mounted Loadbreak Switch
    The 35kV LBOR 4-Position Three Phase Pad Mounted Loadbreak Switch is a robust medium-voltage switching assembly designed for pad-mounted transformer systems and compact distribution substations....
First 12 Last
 
Technical Specifications & Electrical Ratings

 

Model Series

Rated Voltage (kV)

Continuous Current (A)

Short-Time Withstand (kA / 3s)

Making Capacity (Peak kA)

Mechanical Endurance

Insulation Configuration

LBS-12 Series

12

630 / 1250

20 / 25

50 / 63

Class M2 (5,000 ops)

Vacuum / Solid Dielectric

LBS-24 Series

24

630

20

50

Class M1 (2,000 ops)

SF6 Sealed Gas / Vacuum

LBS-38 Series

38

630 / 1250

25

65

Class M2 (5,000 ops)

Solid Dielectric

 

Construction, Materials & Insulation System

Current-Carrying Components

Primary conductive paths utilize Electrolytic Tough Pitch (ETP) copper (≥ 99.9% purity) with silver electroplating (≥ 5μm) on all contact interfaces to minimize electrical resistance, thermal rise, and oxidation under continuous full-load operation.

Insulation Assemblies

Incorporates Automatic Pressure Gelation (APG) cast cycloaliphatic epoxy resin components, delivering superior track resistance, high dielectric strength, and minimal partial discharge (≤ 10pC at 1.2 Ur) for reliable performance in high-humidity or coastal environments.

Structural Enclosure & Frame

Fabricated from heavy-gauge structural steel (2.0mm to 3.0mm thickness) via CNC laser cutting and multi-axis bending, finished with electrostatic powder coating engineered to withstand extended salt-spray exposure (ASTM B117 compliance).

Interruption Technology

Enclosed vacuum interrupter bottles or hermetically sealed SF6 gas tanks utilizing tungsten-copper contact tips to safely extinguish electrical arcs within milliseconds during load interruption.

 

 

 

Operating Mechanism & Safety Interlocks

The operating mechanism ensures independent opening and closing speeds, preventing operator-dependent slow-opening arc damage.

 

Mandatory Mechanical Interlocking Logic:

The main loadbreak switch cannot be closed while the downstream earthing switch is in the closed position.

The earthing switch cannot be operated when the main switching contacts are closed.

Mechanical interlocking prevents improper operating sequences during maintenance.

 

Operational Features:

Manual spring-stored energy operation or motorized spring-charging options.

Auxiliary contact arrangements (NO/NC) available for remote switch position indication and electrical interlocking control.

24kV 630A 3P 2 Position IEEE Loadbreak Switch suppliers

 

25kV 630A Single Phase Flip Type Transformer Loadbreak

 

Manufacturing Process & Factory Quality Control

Professional buyers evaluate manufacturing precision and inspection rigor. Production workflows adhere to strict quality management standards.


Dimensional Precision: Structural frames are processed via CNC fiber laser cutting and robotic welding, maintaining tight dimensional tolerances to ensure effortless switchgear integration.


Routine Testing (100% FAT): Every completed unit undergoes mandatory factory acceptance testing, including:
Power frequency withstand voltage test (1-minute dielectric insulation check).
Main circuit DC resistance measurement (≤ 50 μΩ).
Mechanical operation and interlocking sequence verification (minimum 50 consecutive cycles).


Standards & Compliance: Designed, manufactured, and tested in accordance with IEC 62271-103 and applicable IEEE standards for medium-voltage switches and switchgear assemblies. Type-test reports are available upon request for project submittals.

 

Customization & Engineering Integration

 

 

Mechanical Compatibility

Flexible phase-to-phase spacing (ranging from 150mm to 275mm), adjustable mounting brackets, and customized drive-shaft extensions designed to fit existing or legacy switchgear layouts (Retrofit friendly).

 

Control & SCADA Integration

Motorized operating mechanisms configured for various DC control voltages, supporting remote telecontrol and substation automation networks.

 

Engineering Deliverables

2D dimensional drawings, 3D STEP CAD models, electrical wiring schematics, and certified routine test reports supplied prior to dispatch.

 

 

 

Frequently Asked Questions

 

 

Q: What is the operational distinction between a loadbreak switch and a circuit breaker?

A: A loadbreak switch is designed to make, carry, and interrupt normal operational load currents. Its short-circuit making and withstand capabilities are rated to specific limits, and it typically works alongside backup current-limiting fuses. A circuit breaker possesses high fault-interrupting capacity to autonomously clear heavy short-circuit fault currents within a protection relay scheme.

Q: Can a medium-voltage loadbreak switch be installed in an existing switchgear panel for retrofitting?

A: Yes. However, compatibility must be verified through engineering review. Key parameters such as rated voltage, continuous current, pole spacing, mounting dimensions, terminal orientation, and mechanical interlocking requirements must match the existing enclosure layout.

Q: What maintenance is required for vacuum versus SF6-insulated variants?

A: Vacuum-interrupter models are practically maintenance-free regarding the switching unit, rated for up to 5,000 mechanical operations. SF6-sealed variants require periodic pressure monitoring via built-in pressure gauges or density switches to verify gas integrity over their operational lifespan.

Q: Are certified type-test and routine-test reports available for project bidding?

A: Yes. Comprehensive routine test reports are provided with every production batch. Type-test reports covering dielectric performance, temperature rise, short-time withstand current, and mechanical endurance are available for formal engineering submittals and utility pre-qualification.

Q: What technical details are needed to select the correct model?

A: To determine the optimal configuration, please provide your system rated voltage, continuous current, short-circuit requirements, installation type (indoor/outdoor or enclosure type), operation preference (manual or motorized control voltage), and any existing dimensional constraints or standards compliance requirements.

Q: What are the typical production lead times?

A: Standard catalog configurations typically ship within 3 to 4 weeks. Customized busbar adaptations, specialized mounting brackets, or custom control wiring harnesses generally require 6 to 8 weeks, inclusive of 3D drawing sign-off and prototype verification.

With abundant experience, Wenzhou Best Imp. & Exp. is one of the most professional loadbreak switch manufacturers and suppliers in China. Please feel free to buy durable loadbreak switch made in China here from our factory. Quality products and good service are available.

24kV 630A 3P 2 Position IEEE Loadbreak Switch, 35kV Oil Immersed Loadbreak Switch, loadbreak switch
Send Inquiry