Product Overview & Application Scope
A Medium Voltage Loadbreak Switch (LBS) is a mechanical switching device engineered to make, carry, and interrupt specified normal load currents in medium-voltage power distribution systems. It controls distribution circuits and safely isolates electrical equipment during scheduled operational switching.
Depending on its configuration and rated characteristics, the loadbreak switch provides specified short-circuit making and short-time withstand capabilities. For heavy short-circuit fault interruption, it operates in coordination with downstream protective devices such as current-limiting fuses or upstream circuit breakers.
Standard voltage configurations cover 12kV, 24kV, and 38kV product classes for modern distribution networks.
-
24kV 630A 3P 2 Position IEEE Loadbreak SwitchThe 24kV 630A Three Phase Oil Immersed Loadbreak Switch is engineered for medium-voltage power distribution systems requiring dependable three-phase load control inside oil-filled transformers....
-
Four-Position Oil-Immersed Loadbreak SwitchThe Four-Position Oil-Immersed Loadbreak Switch is designed for medium-voltage oil-filled distribution transformers, providing flexible circuit selection and switching functions for primary-side...
-
25kV 630A Single Phase Flip Type Transformer LoadbreakThe 24kV 630A Oil Immersed Loadbreak Switch is a critical switching device used in medium-voltage distribution transformer systems. It is designed to safely make and break load current under...
-
25kV 630A Two Position Loadbreak SwitchThe 24kV 630A Single Phase Oil Immersed Loadbreak Switch is a specialized switching device developed for medium-voltage oil-filled transformer applications. It enables safe switching and...
-
630A 24KV Flip Type ANSI Load Break SwitchThe 24kV 630A Single Phase Oil Immersed Loadbreak Switch is a specialized switching device developed for medium-voltage oil-filled transformer applications. It enables safe switching and...
-
35kV Oil Immersed Loadbreak SwitchThe 35kV Oil Immersed Loadbreak Switch is a medium-voltage switching component developed for safe and efficient current switching inside oil-filled electrical equipment. It is widely utilized in...
-
630A 40.5kV Pad Mounted Transformer Loadbreak SwitchThe two-position series oil-immersed load switch is suitable for combined transformers with an AC frequency of 50/60 Hz and a maximum voltage of 40.5 kV or below. It serves as a control device for...
-
630A 35KV 2 Pos Oil Loadbreak SwitchThe 630A 35kV 2 Position Flip Top Type Oil Loadbreak Switch is a medium-voltage switching solution developed for oil-insulated transformer systems and compact power distribution equipment....
-
630A 35KV 4 Position Oil Loadbreak SwitchThe 630A 35kV 4 Position Oil Loadbreak Switch is a high-performance medium-voltage switching device engineered for oil-filled transformer applications and compact electrical distribution systems....
-
35kV Four Position Loadbreak SwitchThe 35kV Four Position Loadbreak Switch switch is used in combination transformers. The load switch is available in four-position, with the four-position switch further classified into T-type,...
-
25kV Oil Lbor SwitchThe two-position oil-immersed load switch is mainly used in pad mounted transformers. It has a spring operating mechanism and is a three-phase switch, capable of performing load opening and...
-
35kV Lbor 4 Position Pad Mounted Loadbreak SwitchThe 35kV LBOR 4-Position Three Phase Pad Mounted Loadbreak Switch is a robust medium-voltage switching assembly designed for pad-mounted transformer systems and compact distribution substations....
Technical Specifications & Electrical Ratings
|
Model Series |
Rated Voltage (kV) |
Continuous Current (A) |
Short-Time Withstand (kA / 3s) |
Making Capacity (Peak kA) |
Mechanical Endurance |
Insulation Configuration |
|
LBS-12 Series |
12 |
630 / 1250 |
20 / 25 |
50 / 63 |
Class M2 (5,000 ops) |
Vacuum / Solid Dielectric |
|
LBS-24 Series |
24 |
630 |
20 |
50 |
Class M1 (2,000 ops) |
SF6 Sealed Gas / Vacuum |
|
LBS-38 Series |
38 |
630 / 1250 |
25 |
65 |
Class M2 (5,000 ops) |
Solid Dielectric |
Construction, Materials & Insulation System
Current-Carrying Components
Primary conductive paths utilize Electrolytic Tough Pitch (ETP) copper (≥ 99.9% purity) with silver electroplating (≥ 5μm) on all contact interfaces to minimize electrical resistance, thermal rise, and oxidation under continuous full-load operation.
Insulation Assemblies
Incorporates Automatic Pressure Gelation (APG) cast cycloaliphatic epoxy resin components, delivering superior track resistance, high dielectric strength, and minimal partial discharge (≤ 10pC at 1.2 Ur) for reliable performance in high-humidity or coastal environments.
Structural Enclosure & Frame
Fabricated from heavy-gauge structural steel (2.0mm to 3.0mm thickness) via CNC laser cutting and multi-axis bending, finished with electrostatic powder coating engineered to withstand extended salt-spray exposure (ASTM B117 compliance).
Interruption Technology
Enclosed vacuum interrupter bottles or hermetically sealed SF6 gas tanks utilizing tungsten-copper contact tips to safely extinguish electrical arcs within milliseconds during load interruption.
The operating mechanism ensures independent opening and closing speeds, preventing operator-dependent slow-opening arc damage.
Mandatory Mechanical Interlocking Logic:
The main loadbreak switch cannot be closed while the downstream earthing switch is in the closed position.
The earthing switch cannot be operated when the main switching contacts are closed.
Mechanical interlocking prevents improper operating sequences during maintenance.
Operational Features:
Manual spring-stored energy operation or motorized spring-charging options.
Auxiliary contact arrangements (NO/NC) available for remote switch position indication and electrical interlocking control.


Professional buyers evaluate manufacturing precision and inspection rigor. Production workflows adhere to strict quality management standards.
Dimensional Precision: Structural frames are processed via CNC fiber laser cutting and robotic welding, maintaining tight dimensional tolerances to ensure effortless switchgear integration.
Routine Testing (100% FAT): Every completed unit undergoes mandatory factory acceptance testing, including:
Power frequency withstand voltage test (1-minute dielectric insulation check).
Main circuit DC resistance measurement (≤ 50 μΩ).
Mechanical operation and interlocking sequence verification (minimum 50 consecutive cycles).
Standards & Compliance: Designed, manufactured, and tested in accordance with IEC 62271-103 and applicable IEEE standards for medium-voltage switches and switchgear assemblies. Type-test reports are available upon request for project submittals.
Customization & Engineering Integration
Mechanical Compatibility
Flexible phase-to-phase spacing (ranging from 150mm to 275mm), adjustable mounting brackets, and customized drive-shaft extensions designed to fit existing or legacy switchgear layouts (Retrofit friendly).
Control & SCADA Integration
Motorized operating mechanisms configured for various DC control voltages, supporting remote telecontrol and substation automation networks.
Engineering Deliverables
2D dimensional drawings, 3D STEP CAD models, electrical wiring schematics, and certified routine test reports supplied prior to dispatch.
Frequently Asked Questions
With abundant experience, Wenzhou Best Imp. & Exp. is one of the most professional loadbreak switch manufacturers and suppliers in China. Please feel free to buy durable loadbreak switch made in China here from our factory. Quality products and good service are available.
24kV 630A 3P 2 Position IEEE Loadbreak Switch, 35kV Oil Immersed Loadbreak Switch, loadbreak switch